108.473—Foam system components.
        
        (a) 
         Each foam agent, each tank for a foam agent, each discharge outlet, each control, and each valve for the operation of a foam extinguishing system must be approved by the Commandant.
    
    
        
        (b) 
         Each foam agent tank and each control and valve for the operation of a foam extinguishing system with outlets in a space must be outside the space and must not be in a space that may become inaccessible if a fire occurs in the space.
    
    
        
        (c) 
         Each control for a foam extinguishing system with outlets in a space must be near a main escape from the space.