111.30-19—Buses and wiring.
               		
               		
               	 	
               	 	
               	 	
               	 		
    
        
        (a) General.
         Each bus must meet the requirements of either—
     
    
        
        (1) 
         Section 7.10 of IEEE 45-1998 (incorporated by reference; see  46 CFR 110.10-1 ); or
     
    
        
        (2) 
         IEC 60092-302 (clause 7) (incorporated by reference; see  46 CFR 110.10-1 ).
     
    
        
        (b) Wiring.
         Instrumentation and control wiring must be—
     
    
        
        (1) 
         Suitable for installation within in a switchboard enclosure and be rated at 90 °C or higher;
     
    
    
        
        (3) 
         No. 14 AWG (2.10 mm 2) or larger or must be ribbon cable or similar conductor size cable recommended for use in low-power instrumentation, monitoring, or control circuits by the equipment manufacturer;
     
    
        
        (4) 
         Flame-retardant meeting test VW-1 of UL 1581 or IEC 332-1 (both incorporated by reference; see  46 CFR 110.10-1 ); and
     
    
        
        (5) 
         Extra flexible, if used on a hinged panel.
     
    
        
            Code of Federal Regulations
        
        [CGD 94-108, 61 FR 28278, June 4, 1996, as amended at 62 FR 23908, May 1, 1997; USCG-2003-16630, 73 FR 65197, Oct. 31, 2008]