118.420—Pre-engineered fixed gas fire extinguishing systems.
        
        (2) 
         Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector;
    
    
        
        (3) 
         Automatically shut down all power ventilation systems and all engines that draw intake air from within the protection space; and
    
    
    
        
        (b) 
         A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station:
    
    
    
    
        
        (3) 
         A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section.
    
    
        
        (c) 
         Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.