129.326—Dual-voltage generators.
               		
               		
               	 	
               	 	
               	 	
               	 		
    
         If a dual-voltage generator is installed on an OSV—
    
    
        
        (a) 
         The neutral of the dual-voltage system must be solidly grounded at the switchboard's neutral bus and be accessible for checking the insulation resistance of the generator; and
     
    
        
        (b) 
         Ground detection must be provided that—
     
    
        
        (1) 
         For an alternating-current system, complies with  § 111.05-27 of this chapter; and
     
    
        
        (2) 
         For a direct-current system, complies with  § 111.05-29 of this chapter.