153.350—Location of B/3 vent discharges.
         Except as prescribed in  § 153.353, a
    
    B/3 venting system must discharge:
    
    
    
    
        
        (3) 
         6m (approx. 19.7 ft) above a walkway, if the walkway is within a 6m (approx. 19.7 ft) horizontal radius from the vent discharge.
    
    
        
        (b) 
         At least 15m (approx. 49.2 ft) from air intakes for, or openings into, accommodation and service spaces.
    
    [CGD 78-128, 47 FR 21208, May 17, 1982; 47 FR 27293, June 24, 1982]