162.050-17—Separator test rig.
        
        (a) 
         This section contains requirements for test rigs used in approval testing of separators. A diagram of a typical test rig is shown in Figure 162.050-17(a).
    
    Code of Federal Regulations
        
        (2) 
         Have a delivery capacity of at least 1.5 times the maximum throughput at which the separator being tested is designed to operate;
    
    
        
        (3) 
         Have a maximum delivery pressure that is equal to or greater than the maximum influent pressure at which the separator is designed to operate; and
    
    
        
        (4) 
         Have either bypass piping to its suction side or a throttle valve or orifice on its discharge side.
    
    
    
    
    
    
        
        (d) 
         Each sample point on a test rig must meet the design requirements described in Figure 162.050-17(d) and must be in a vertical portion of the test rig piping.
    
    Code of Federal Regulations
[CGD 76-088a, 44 FR 53359, Sept. 13, 1979, as amended by USCG-2004-18939, 74 FR 3384, Jan. 16, 2009]