183.324—Dual voltage generators.
        
        (1) 
         The neutral of a dual voltage system must be solidly connected at the switchboard's neutral bus; and
    
    
    
        
        (b) 
         The neutral of a dual voltage system must be accessible for checking the insulation resistance of the generator to ground before the generator is connected to the bus.