192.115—Temperature derating factor ( T ) for steel pipe.
         The temperature derating factor to be used in the design formula in  § 192.105 is determined as follows:
    
    | Gas temperature in degrees Fahrenheit (Celsius) | Temperature derating factor (T) | 
|---|---|
| 250 °F (121 °C) or less | 1.000 | 
| 300 °F (149 °C) | 0.967 | 
| 350 °F (177 °C) | 0.933 | 
| 400 °F (204 °C) | 0.900 | 
| 450 °F (232 °C) | 0.867 | 
For intermediate gas temperatures, the derating factor is determined by interpolation.
    [35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-85, 63 FR 37502, July 13, 1998]